IECC CLIMATE ZONE 5B // Cool · Dry

Climate Zone 5B Insulation R-Values, Window U-Factor & SHGC Requirements

Side-by-side IECC 2021 vs 2024 residential REScheck and commercial COMcheck thermal envelope specifications for Climate Zone 5B (Denver, CO, Salt Lake City, UT, Boise, ID, Spokane, WA, Reno, NV).

IECC 2021 vs 2024 Thermal Envelope Specification Table — Climate Zone 5B
Assembly Component2021 IECC Residential2024 IECC Residential2021 COMcheck (Com)2024 COMcheck (Com)
Fenestration Max U-Factor0.300.290.360.35
Glazing Max SHGCNR (N/A)NR (N/A)0.380.38
Ceiling / Roof R-Value (Max U)R-60 (0.0240)R-60 (0.0230)R-30ci (above deck) (0.0320)R-30ci (above deck) (0.0307)
Exterior Wall R-Value (Max U)R-20+5ci or R-13+10ci (0.0450)R-20+5ci or R-13+10ci (0.0432)R-13 + 10ci (steel) (0.0550)R-13 + 10ci (steel) (0.0528)
Floor Insulation (Max U)R-30 (0.0330)R-30 (0.0317)U ≤ 0.0520U ≤ 0.0499
Basement Wall R-ValueR-15ci or R-19R-15ci or R-19C402 Below-GradeC402 Below-Grade
Slab Edge R-Value (Max F)R-10ci (4 ft) (F ≤ 0.51)R-10ci (4 ft) (F ≤ 0.51)F ≤ 0.51F ≤ 0.51
Opaque Door Max U-Factor0.300.290.370.35
Zone 5B Solar Heat Gain Coefficient (SHGC) Guidance

High-altitude cool-dry: Residential SHGC is NR (N/A) to allow passive winter solar gain; commercial max SHGC 0.38.

Representative US Cities in Climate Zone 5B
Denver, COSalt Lake City, UTBoise, IDSpokane, WAReno, NV

US States Containing IECC Climate Zone 5B (10)

Permit & Energy Code FAQ

What are the residential wall and ceiling R-Values for IECC Climate Zone 5B?

Under 2021 IECC in Climate Zone 5B, prescriptive residential ceilings require R-60 (max U 0.0240) and wood-framed exterior walls require R-20+5ci or R-13+10ci (max U 0.0450).

What is the maximum window U-Factor and SHGC in Climate Zone 5B?

For residential construction under 2021 IECC, Zone 5B requires fenestration U-Factor <= 0.30 (tightening to 0.29 under 2024 IECC modeling) with SHGC NR (N/A). High-altitude cool-dry: Residential SHGC is NR (N/A) to allow passive winter solar gain; commercial max SHGC 0.38.

How does commercial COMcheck differ from residential REScheck in Zone 5B?

Commercial buildings in Zone 5B use steel-framed/mass wall and above-deck roof assemblies (window U <= 0.36, SHGC <= 0.38, roof R-30ci (above deck), wall R-13 + 10ci (steel)) and cap prescriptive Window-to-Wall Ratio at 30%.

Explore All 15 IECC Climate Zones