IECC CLIMATE ZONE 4A // Mixed · Humid

Climate Zone 4A Insulation R-Values, Window U-Factor & SHGC Requirements

Side-by-side IECC 2021 vs 2024 residential REScheck and commercial COMcheck thermal envelope specifications for Climate Zone 4A (New York, NY, Washington, DC, Philadelphia, PA, Nashville, TN, Kansas City, MO).

IECC 2021 vs 2024 Thermal Envelope Specification Table — Climate Zone 4A
Assembly Component2021 IECC Residential2024 IECC Residential2021 COMcheck (Com)2024 COMcheck (Com)
Fenestration Max U-Factor0.300.290.360.35
Glazing Max SHGCNR (N/A)NR (N/A)0.360.36
Ceiling / Roof R-Value (Max U)R-60 (0.0240)R-60 (0.0230)R-30ci (above deck) (0.0320)R-30ci (above deck) (0.0307)
Exterior Wall R-Value (Max U)R-20+5ci or R-13+10ci (0.0450)R-20+5ci or R-13+10ci (0.0432)R-13 + 7.5ci (steel) (0.0640)R-13 + 7.5ci (steel) (0.0614)
Floor Insulation (Max U)R-19 (0.0470)R-19 (0.0451)U ≤ 0.0520U ≤ 0.0499
Basement Wall R-ValueR-10ci or R-13R-10ci or R-13C402 Below-GradeC402 Below-Grade
Slab Edge R-Value (Max F)R-10ci (4 ft) (F ≤ 0.52)R-10ci (4 ft) (F ≤ 0.52)F ≤ 0.52F ≤ 0.52
Opaque Door Max U-Factor0.300.290.370.35
Zone 4A Solar Heat Gain Coefficient (SHGC) Guidance

NR in EnvelopeCheck residential UA engine (prescriptive IECC 2021 Table R402.1.3 lists 0.40 for 4A; 0.36 commercial).

Representative US Cities in Climate Zone 4A
New York, NYWashington, DCPhiladelphia, PANashville, TNKansas City, MO

US States Containing IECC Climate Zone 4A (19)

Permit & Energy Code FAQ

What are the residential wall and ceiling R-Values for IECC Climate Zone 4A?

Under 2021 IECC in Climate Zone 4A, prescriptive residential ceilings require R-60 (max U 0.0240) and wood-framed exterior walls require R-20+5ci or R-13+10ci (max U 0.0450).

What is the maximum window U-Factor and SHGC in Climate Zone 4A?

For residential construction under 2021 IECC, Zone 4A requires fenestration U-Factor <= 0.30 (tightening to 0.29 under 2024 IECC modeling) with SHGC NR (N/A). NR in EnvelopeCheck residential UA engine (prescriptive IECC 2021 Table R402.1.3 lists 0.40 for 4A; 0.36 commercial).

How does commercial COMcheck differ from residential REScheck in Zone 4A?

Commercial buildings in Zone 4A use steel-framed/mass wall and above-deck roof assemblies (window U <= 0.36, SHGC <= 0.36, roof R-30ci (above deck), wall R-13 + 7.5ci (steel)) and cap prescriptive Window-to-Wall Ratio at 30%.

Explore All 15 IECC Climate Zones