IECC CLIMATE ZONE 3B // Warm · Dry

Climate Zone 3B Insulation R-Values, Window U-Factor & SHGC Requirements

Side-by-side IECC 2021 vs 2024 residential REScheck and commercial COMcheck thermal envelope specifications for Climate Zone 3B (Los Angeles, CA, Las Vegas, NV, El Paso, TX, Sacramento, CA, Lubbock, TX).

IECC 2021 vs 2024 Thermal Envelope Specification Table — Climate Zone 3B
Assembly Component2021 IECC Residential2024 IECC Residential2021 COMcheck (Com)2024 COMcheck (Com)
Fenestration Max U-Factor0.300.290.420.40
Glazing Max SHGC0.250.250.250.25
Ceiling / Roof R-Value (Max U)R-49 (0.0260)R-49 (0.0250)R-25ci (above deck) (0.0390)R-25ci (above deck) (0.0374)
Exterior Wall R-Value (Max U)R-20+0 or R-13+5ci (0.0600)R-20+0 or R-13+5ci (0.0576)R-13 + 5ci (steel) (0.0770)R-13 + 5ci (steel) (0.0739)
Floor Insulation (Max U)R-19 (0.0470)R-19 (0.0451)U ≤ 0.0740U ≤ 0.0710
Basement Wall R-ValueR-5ci or R-13R-5ci or R-13C402 Below-GradeC402 Below-Grade
Slab Edge R-Value (Max F)R-10ci (2 ft) (F ≤ 0.54)R-10ci (2 ft) (F ≤ 0.54)F ≤ 0.54F ≤ 0.54
Opaque Door Max U-Factor0.300.290.610.59
Zone 3B Solar Heat Gain Coefficient (SHGC) Guidance

Warm-dry cooling control: SHGC <= 0.25 (California Title 24 caps warm zones at 0.23).

Representative US Cities in Climate Zone 3B
Los Angeles, CALas Vegas, NVEl Paso, TXSacramento, CALubbock, TX

US States Containing IECC Climate Zone 3B (6)

Permit & Energy Code FAQ

What are the residential wall and ceiling R-Values for IECC Climate Zone 3B?

Under 2021 IECC in Climate Zone 3B, prescriptive residential ceilings require R-49 (max U 0.0260) and wood-framed exterior walls require R-20+0 or R-13+5ci (max U 0.0600).

What is the maximum window U-Factor and SHGC in Climate Zone 3B?

For residential construction under 2021 IECC, Zone 3B requires fenestration U-Factor <= 0.30 (tightening to 0.29 under 2024 IECC modeling) with SHGC 0.25. Warm-dry cooling control: SHGC <= 0.25 (California Title 24 caps warm zones at 0.23).

How does commercial COMcheck differ from residential REScheck in Zone 3B?

Commercial buildings in Zone 3B use steel-framed/mass wall and above-deck roof assemblies (window U <= 0.42, SHGC <= 0.25, roof R-25ci (above deck), wall R-13 + 5ci (steel)) and cap prescriptive Window-to-Wall Ratio at 30%.

Explore All 15 IECC Climate Zones