IECC CLIMATE ZONE 6B // Cold · Dry

Climate Zone 6B Insulation R-Values, Window U-Factor & SHGC Requirements

Side-by-side IECC 2021 vs 2024 residential REScheck and commercial COMcheck thermal envelope specifications for Climate Zone 6B (Billings, MT, Bozeman, MT, Cheyenne, WY, Idaho Falls, ID).

IECC 2021 vs 2024 Thermal Envelope Specification Table — Climate Zone 6B
Assembly Component2021 IECC Residential2024 IECC Residential2021 COMcheck (Com)2024 COMcheck (Com)
Fenestration Max U-Factor0.300.290.340.33
Glazing Max SHGCNR (N/A)NR (N/A)0.400.40
Ceiling / Roof R-Value (Max U)R-60 (0.0240)R-60 (0.0230)R-30ci (above deck) (0.0320)R-30ci (above deck) (0.0307)
Exterior Wall R-Value (Max U)R-20+5ci or R-13+10ci (0.0450)R-20+5ci or R-13+10ci (0.0432)R-13 + 12.5ci (steel) (0.0490)R-13 + 12.5ci (steel) (0.0470)
Floor Insulation (Max U)R-30 (0.0330)R-30 (0.0317)U ≤ 0.0510U ≤ 0.0490
Basement Wall R-ValueR-15ci or R-19R-15ci or R-19C402 Below-GradeC402 Below-Grade
Slab Edge R-Value (Max F)R-10ci (4 ft) (F ≤ 0.51)R-10ci (4 ft) (F ≤ 0.51)F ≤ 0.51F ≤ 0.51
Opaque Door Max U-Factor0.300.290.370.35
Zone 6B Solar Heat Gain Coefficient (SHGC) Guidance

Cold mountain-dry: Residential SHGC is NR (N/A); commercial max window U-Factor drops to 0.34.

Representative US Cities in Climate Zone 6B
Billings, MTBozeman, MTCheyenne, WYIdaho Falls, ID

US States Containing IECC Climate Zone 6B (6)

Permit & Energy Code FAQ

What are the residential wall and ceiling R-Values for IECC Climate Zone 6B?

Under 2021 IECC in Climate Zone 6B, prescriptive residential ceilings require R-60 (max U 0.0240) and wood-framed exterior walls require R-20+5ci or R-13+10ci (max U 0.0450).

What is the maximum window U-Factor and SHGC in Climate Zone 6B?

For residential construction under 2021 IECC, Zone 6B requires fenestration U-Factor <= 0.30 (tightening to 0.29 under 2024 IECC modeling) with SHGC NR (N/A). Cold mountain-dry: Residential SHGC is NR (N/A); commercial max window U-Factor drops to 0.34.

How does commercial COMcheck differ from residential REScheck in Zone 6B?

Commercial buildings in Zone 6B use steel-framed/mass wall and above-deck roof assemblies (window U <= 0.34, SHGC <= 0.40, roof R-30ci (above deck), wall R-13 + 12.5ci (steel)) and cap prescriptive Window-to-Wall Ratio at 30%.

Explore All 15 IECC Climate Zones