IECC CLIMATE ZONE 3A // Warm · Humid
Climate Zone 3A Insulation R-Values, Window U-Factor & SHGC Requirements
Side-by-side IECC 2021 vs 2024 residential REScheck and commercial COMcheck thermal envelope specifications for Climate Zone 3A (Dallas, TX, Atlanta, GA, Charlotte, NC, Charleston, SC, Birmingham, AL).
| Assembly Component | 2021 IECC Residential | 2024 IECC Residential | 2021 COMcheck (Com) | 2024 COMcheck (Com) |
|---|---|---|---|---|
| Fenestration Max U-Factor | 0.30 | 0.29 | 0.42 | 0.40 |
| Glazing Max SHGC | 0.25 | 0.25 | 0.25 | 0.25 |
| Ceiling / Roof R-Value (Max U) | R-49 (0.0260) | R-49 (0.0250) | R-25ci (above deck) (0.0390) | R-25ci (above deck) (0.0374) |
| Exterior Wall R-Value (Max U) | R-20+0 or R-13+5ci (0.0600) | R-20+0 or R-13+5ci (0.0576) | R-13 + 5ci (steel) (0.0770) | R-13 + 5ci (steel) (0.0739) |
| Floor Insulation (Max U) | R-19 (0.0470) | R-19 (0.0451) | U ≤ 0.0740 | U ≤ 0.0710 |
| Basement Wall R-Value | R-5ci or R-13 | R-5ci or R-13 | C402 Below-Grade | C402 Below-Grade |
| Slab Edge R-Value (Max F) | R-10ci (2 ft) (F ≤ 0.54) | R-10ci (2 ft) (F ≤ 0.54) | F ≤ 0.54 | F ≤ 0.54 |
| Opaque Door Max U-Factor | 0.30 | 0.29 | 0.61 | 0.59 |
Balanced warm-humid climate: SHGC <= 0.25 and fenestration U-Factor <= 0.30 under 2021 IECC.
US States Containing IECC Climate Zone 3A (10)
Alabama (AL)
2015 IECC (State Amended)
Arkansas (AR)
2014 Arkansas Energy Code (2009/2015 IECC base)
Georgia (GA)
2015 IECC (Georgia State Supplements)
Louisiana (LA)
2021 IECC (Louisiana State Uniform Construction Code)
Mississippi (MS)
2018 IECC (Local AHJ / State Buildings)
North Carolina (NC)
2018 NC Energy Conservation Code (2015/2018 IECC)
Oklahoma (OK)
2018 IRC / IECC (Oklahoma OUBCC Amended)
South Carolina (SC)
2009 / 2021 IECC (SC Energy Standard)
Tennessee (TN)
2018 IECC (Tennessee State Amended)
Texas (TX)
2015 / 2021 IECC (SECO Statewide; Austin/Houston/Dallas 2021)
Permit & Energy Code FAQ
What are the residential wall and ceiling R-Values for IECC Climate Zone 3A?
Under 2021 IECC in Climate Zone 3A, prescriptive residential ceilings require R-49 (max U 0.0260) and wood-framed exterior walls require R-20+0 or R-13+5ci (max U 0.0600).
What is the maximum window U-Factor and SHGC in Climate Zone 3A?
For residential construction under 2021 IECC, Zone 3A requires fenestration U-Factor <= 0.30 (tightening to 0.29 under 2024 IECC modeling) with SHGC 0.25. Balanced warm-humid climate: SHGC <= 0.25 and fenestration U-Factor <= 0.30 under 2021 IECC.
How does commercial COMcheck differ from residential REScheck in Zone 3A?
Commercial buildings in Zone 3A use steel-framed/mass wall and above-deck roof assemblies (window U <= 0.42, SHGC <= 0.25, roof R-25ci (above deck), wall R-13 + 5ci (steel)) and cap prescriptive Window-to-Wall Ratio at 30%.
Explore All 15 IECC Climate Zones
Verify Your Climate Zone 3A Blueprints in Minutes
Upload permit PDFs or CSV schedules to calculate net wall areas, check Zone 3A U-Factor & SHGC compliance, and export DOE REScheck (.rck) or PNNL COMcheck payloads.