Climate Zone 8 Insulation R-Values, Window U-Factor & SHGC Requirements

Side-by-side IECC 2021 vs 2024 residential REScheck and commercial COMcheck thermal envelope specifications for Climate Zone 8 (Fairbanks, AK, Utqiagvik, AK, Bethel, AK, Nome, AK).

IECC 2021 vs 2024 Thermal Envelope Specification Table — Climate Zone 8
Assembly Component2021 IECC Residential2024 IECC Residential2021 COMcheck (Com)2024 COMcheck (Com)
Fenestration Max U-Factor0.300.290.260.25
Glazing Max SHGCNR (N/A)NR (N/A)0.450.45
Ceiling / Roof R-Value (Max U)R-60 (0.0240)R-60 (0.0230)R-35ci (above deck) (0.0280)R-35ci (above deck) (0.0269)
Exterior Wall R-Value (Max U)R-20+5ci or R-13+10ci (0.0450)R-20+5ci or R-13+10ci (0.0432)R-13 + 18.8ci (steel) (0.0370)R-13 + 18.8ci (steel) (0.0355)
Floor Insulation (Max U)R-38 (0.0280)R-38 (0.0269)U ≤ 0.0370U ≤ 0.0355
Basement Wall R-ValueR-15ci or R-19R-15ci or R-19C402 Below-GradeC402 Below-Grade
Slab Edge R-Value (Max F)R-10ci (4 ft) (F ≤ 0.51)R-10ci (4 ft) (F ≤ 0.51)F ≤ 0.43F ≤ 0.43
Opaque Door Max U-Factor0.300.290.370.35
Zone 8 Solar Heat Gain Coefficient (SHGC) Guidance

Subarctic envelope: Residential SHGC is NR (N/A); commercial wall U <= 0.037 and window U <= 0.26.

Representative US Cities in Climate Zone 8
Fairbanks, AKUtqiagvik, AKBethel, AKNome, AK

US States Containing IECC Climate Zone 8 (1)

Permit & Energy Code FAQ

What are the residential wall and ceiling R-Values for IECC Climate Zone 8?

Under 2021 IECC in Climate Zone 8, prescriptive residential ceilings require R-60 (max U 0.0240) and wood-framed exterior walls require R-20+5ci or R-13+10ci (max U 0.0450).

What is the maximum window U-Factor and SHGC in Climate Zone 8?

For residential construction under 2021 IECC, Zone 8 requires fenestration U-Factor <= 0.30 (tightening to 0.29 under 2024 IECC modeling) with SHGC NR (N/A). Subarctic envelope: Residential SHGC is NR (N/A); commercial wall U <= 0.037 and window U <= 0.26.

How does commercial COMcheck differ from residential REScheck in Zone 8?

Commercial buildings in Zone 8 use steel-framed/mass wall and above-deck roof assemblies (window U <= 0.26, SHGC <= 0.45, roof R-35ci (above deck), wall R-13 + 18.8ci (steel)) and cap prescriptive Window-to-Wall Ratio at 30%.

Explore All 15 IECC Climate Zones

Verify Your Climate Zone 8 Blueprints in Minutes

Upload permit PDFs or CSV schedules to calculate net wall areas, check Zone 8 U-Factor & SHGC compliance, and export DOE REScheck (.rck) or PNNL COMcheck payloads.

Open Takeoff Workbench