IECC CLIMATE ZONE 6A // Cold · Humid
Climate Zone 6A Insulation R-Values, Window U-Factor & SHGC Requirements
Side-by-side IECC 2021 vs 2024 residential REScheck and commercial COMcheck thermal envelope specifications for Climate Zone 6A (Minneapolis, MN, Milwaukee, WI, Burlington, VT, Portland, ME, Sioux Falls, SD).
| Assembly Component | 2021 IECC Residential | 2024 IECC Residential | 2021 COMcheck (Com) | 2024 COMcheck (Com) |
|---|---|---|---|---|
| Fenestration Max U-Factor | 0.30 | 0.29 | 0.34 | 0.33 |
| Glazing Max SHGC | NR (N/A) | NR (N/A) | 0.40 | 0.40 |
| Ceiling / Roof R-Value (Max U) | R-60 (0.0240) | R-60 (0.0230) | R-30ci (above deck) (0.0320) | R-30ci (above deck) (0.0307) |
| Exterior Wall R-Value (Max U) | R-20+5ci or R-13+10ci (0.0450) | R-20+5ci or R-13+10ci (0.0432) | R-13 + 12.5ci (steel) (0.0490) | R-13 + 12.5ci (steel) (0.0470) |
| Floor Insulation (Max U) | R-30 (0.0330) | R-30 (0.0317) | U ≤ 0.0510 | U ≤ 0.0490 |
| Basement Wall R-Value | R-15ci or R-19 | R-15ci or R-19 | C402 Below-Grade | C402 Below-Grade |
| Slab Edge R-Value (Max F) | R-10ci (4 ft) (F ≤ 0.51) | R-10ci (4 ft) (F ≤ 0.51) | F ≤ 0.51 | F ≤ 0.51 |
| Opaque Door Max U-Factor | 0.30 | 0.29 | 0.37 | 0.35 |
Cold heating-dominated: Residential SHGC is NR (N/A); continuous exterior wall insulation (R-20+5ci / R-13+10ci) drives UA compliance.
US States Containing IECC Climate Zone 6A (10)
Iowa (IA)
2012 / 2015 IECC (State Energy Code)
Maine (ME)
2021 IECC (MUBEC Statewide)
Michigan (MI)
2015 / 2021 IECC (Michigan Energy Code)
Minnesota (MN)
2020 MN Residential Energy Code (2012/2018 IECC base)
New Hampshire (NH)
2018 IECC (NH State Building Code)
New York (NY)
2020 NYECC / NYCECC (NYStretch Ready)
North Dakota (ND)
2021 IECC (ND State Building Code)
South Dakota (SD)
2018 / 2021 IECC (Local AHJ Adoption)
Vermont (VT)
2024 Vermont RBES (2021 IECC+ Stretch)
Wisconsin (WI)
Wisconsin UDC (2009/2015 IECC State Standard)
Permit & Energy Code FAQ
What are the residential wall and ceiling R-Values for IECC Climate Zone 6A?
Under 2021 IECC in Climate Zone 6A, prescriptive residential ceilings require R-60 (max U 0.0240) and wood-framed exterior walls require R-20+5ci or R-13+10ci (max U 0.0450).
What is the maximum window U-Factor and SHGC in Climate Zone 6A?
For residential construction under 2021 IECC, Zone 6A requires fenestration U-Factor <= 0.30 (tightening to 0.29 under 2024 IECC modeling) with SHGC NR (N/A). Cold heating-dominated: Residential SHGC is NR (N/A); continuous exterior wall insulation (R-20+5ci / R-13+10ci) drives UA compliance.
How does commercial COMcheck differ from residential REScheck in Zone 6A?
Commercial buildings in Zone 6A use steel-framed/mass wall and above-deck roof assemblies (window U <= 0.34, SHGC <= 0.40, roof R-30ci (above deck), wall R-13 + 12.5ci (steel)) and cap prescriptive Window-to-Wall Ratio at 30%.